Various studies have shown that noise
exposure—even modest levels of ambient
noise—can negatively affect
learning, especially for young children. To
create cleaner, healthier indoor environments
that lower student and staff absentee
rates and improve teacher retention, advanced,
energy-efficient heating and cooling
systems can help. According to the American
Society for Heating, Refrigeration and
Air Conditioning Engineers, regularly
scheduled maintenance is an important part
of keeping the HVAC system in optimum
working condition.
ASHRAE’s “Advanced Energy Design
Guide for K-12 School Buildings” says
that neglecting preventive maintenance
practices can quickly negate any energy
savings expected from HVAC system design.
It says that filters should be replaced
when pressure drop exceeds manufacturer
recommendations for replacement, or when visual inspection indicates the need
for replacement.
Energy recovery ventilators need to be
cleaned periodically to maintain performance.
Dampers, valves, louvers, and sensors
must all be periodically inspected and
calibrated to ensure proper operation.
This is especially important for outdoor
air dampers and CO2 sensors. Inaccurate
CO2 sensors can cause excessive energy use
or poor IAQ, so they need to be calibrated
as recommended by the manufacturer.
A building automation system can be
used to notify operations and maintenance
staff when preventive maintenance procedures
should be performed. This notification
can be triggered by calendar dates,
run-time hours, the number of times a
piece of equipment has started, or sensors
installed in the system (such as a pressure
switch that indicates when an air filter is
too dirty and needs to be replaced).
Control strategies can be designed to help
reduce energy. Having a setback temperature
for unoccupied periods during the
heating season or a setup temperature
during the cooling season can help to
save energy by avoiding the need to operate
heating, cooling, and ventilation
equipment.
Programmable thermostats allow each
zone to vary the temperature set point
based on time of day and day of the week.
But they also allow occupants to override
these set points or ignore the schedule altogether
(by using the “hold” feature),
which thwarts any potential for energy
savings.
A more sustainable approach is to equip
each zone with a zone temperature sensor
and then use a system-level controller that
coordinates the operation of all components
of the system.
This system-level controller contains time-of-day schedules that define when
different areas of the building are expected
to be unoccupied. During these
times, the system is shut off and the temperature
is allowed to drift away from the
occupied set point.
A pre-occupancy ventilation period
can help purge the building of contaminants
that build up overnight from the
off-gassing of products and packaging
materials. When it is cool at night, it
can also help pre-cool the building.
In humid climates, however, care
should be taken to avoid bringing in
humid outdoor air during unoccupied
periods.
Optimal start uses a system-level controller
to determine the length of time required
to bring each zone from the current
temperature to the occupied set point temperature.
Then, the controller waits as
long as possible before starting the system,
so that the temperature in each zone
reaches occupied set point just in time for
occupancy.
This strategy reduces the number of
hours that the system needs to operate,
and saves energy by avoiding the need to
maintain the indoor temperature at occupied occupied
set point even though the building is
unoccupied.
Air Handlers
For Multiple-Zone, VAV Air Handlers,
each variable air volume air handler
should have an outdoor air (OA)
intake through which OA is introduced
and mixes with the recirculated air,
prior to being delivered to the zones. Alternatively,
a dedicated OA system
could be used to deliver OA directly to
each zone, to individual dual-duct VAV
terminals that serve each zone, or to the
OA intake of one or more VAV air handlers.
Note that the occupant load, or exit
population, used for egress design to
comply with the fire code is typically
much higher than the zone population
used for ventilation system design. Using
occupant load, rather than zone population,
to calculate ventilation requirements
can result in significant over-ventilation,
oversized HVAC equipment, and excess
energy use.
Buildings with multiple-zone, recirculating
ventilation systems (MZS) can be
designed to account for recirculated OA,
as well as system population diversity,
using the equations found in ASHRAE
Standard 62.1.
In effect, the MZS design approach allows
ventilation air to be calculated on the
basis of how many people are in the building
(system population at design) rather
than the sum of how many people are in
each space (sum-of-peak zone population
at design).
This can reduce the energy required
to condition ventilation air in K-12
schools. ❑
Source: ASHRAE Advanced Energy
Design Guide for K-12 School Buildings.