The faster firefighters can respond,
enter, locate and safely operate in
a building, the sooner they can
put out a fire or mitigate any other potentially
dangerous incident.
Properly positioned fire-fighting
equipment is critical at such scenes. In
particular, ladder trucks and pumpers
need to get close enough to a building to
facilitate access and hose line use.
Many structures are situated on public
streets that provide fire-fighting access.
Others, which are set back from public
streets, have private fire apparatus access
lanes or “fire lanes.” These enable
fire trucks to approach the building and
operate effectively.
There are many considerations for both
public roads and fire lanes: clear width,
clear height, length, turn radius, arrangement,
distance from the building, and
paving materials. In all cases, the most stringent practicable dimensions
should be considered for design,
since future apparatus purchases or
mutual aid apparatus from other jurisdictions
may exceed the specifications
required in a given jurisdiction
at any given time.
OSHA says minimum building
access for fire apparatus is a function
of the access road reaching to within
a certain distance of all portions of
the building’s first floor exterior
walls. This limit in NFPA 1 and the
IFC is 150 feet for buildings without
a complete sprinkler system. For
fully sprinklered buildings, NFPA 1
permits this distance to be increased
to 450 feet; the IFC leaves this decision
up to the discretion of the code
official. Further, NFPA 1 requires that the
road extend to within 50 feet of an exterior
door providing interior access.
The distance from the building to a
road or fire lane is sometimes referred
to as “setback distance.” NFPA 1141
has additional guidelines for access locations
versus building location, with
variations depending upon building
size, height, sprinkler protection, and separation from other buildings.
Perimeter Access
The options available for attacking a
fire increase as more of a building’s
perimeter becomes accessible to fire apparatus.
A concept, known as “frontage
increase,” appears in the IBC and NFPA
5000. If a structure has more than a certain
percentage of its perimeter accessible to fire apparatus, these codes allow
the maximum size of the building
to be increased. Ideally, the full
perimeter would be accessible.
During renovations, designers
should use particular caution to ensure
that the perimeter access continues
to meet the NFPA requirements
of fire and building codes. The original
building site may have been based
on a frontage increase. Changing the
amount of perimeter access can result
in noncompliant building size.
Turnarounds
Long, dead-end fire lanes or roads
should provide a means for fire apparatus
to turn around. Both NFPA
1 and the IFC require turnaround
space for dead-ends that are more than
150 feet long. There are a number of configurations
that facilitate turning maneuvers.
These include, “T-turn,” “Y-turn,”
and round cul-de-sac style arrangements.
Clear Width
The basic clear width requirement for
apparatus access in the IFC and NFPA 1
is 20 feet. NFPA 1141 calls for one-way fire lanes that are 16 feet wide; however,
this applies to roads that do not
abut buildings. A clear width of 20 feet
will allow most aerial apparatus to extend
the outriggers necessary to support
the aerial ladder or elevating platform
while in operation. However, some recently
manufactured aerial apparatus require
24 feet of clear width for outrigger
extension.
Lanes wide enough for apparatus to
pass one another will facilitate developing
and expanding operations. NFPA
1141 contains a 24-foot clear width requirement
for two-way fire lanes. Appendix
D of the IBC calls for a 26-foot clear
width at fire hydrant locations, extending
for a distance of 20 feet in both directions,
as well as a 26-foot width in the
vicinity of buildings that are 30 feet or
more in height (for aerial operations).
NFPA 1141 also contains guidance on access
in parking lots.
Height
The basic requirement for clear height
of fire lanes in the IFC, NFPA 1 and
NFPA 1141 is 13 feet 6 inches. Some
modern aerial apparatus may require 14
feet of clearance. Potential for accumulation
of snow and ice should be factored
into height requirements. The NFPA 1
handbook recommends at least 14 feet in
colder climates. Newer aerial apparatus
may also require additional height. Finally,
avoid overhead wires or other obstructions
when determining fire lane
locations.
In areas with aerial apparatus that may
respond to an emergency, the road or fire
lane should be positioned at a distance
from the building that will accommodate
aerial ladder operation. Access too close
or too far from the building will limit aerial
ladder use. Where a fire lane is parallel
to a building that is more than 30 feet
high, Appendix D of the IFC calls for the
near edge of the lane to be between 15
and 30 feet away from the building.
Marking
Fire lane signage is important, both for
the public and enforcement officials. Examples
include signs, curb painting, or
curb stenciling. A jurisdiction’s requirements
must be followed exactly to ensure
that no-parking provisions are legally enforceable.
The fire service must be able to rapidly
identify and locate a specific building. Address
numbers should be placed on the building facing the street or road on which
the building is addressed. If the building
entry faces a different street, both the
street name and the number should be on
the address sign.
Numbers should be large enough to
read from the street or road. If this is not
possible due to the location of the building
or due to obstructions, additional signs
should be provided. The IFC specifies that
address numbers be a minimum of 4
inches high. Some jurisdictions have a higher minimum height requirement, especially
for commercial properties. The
number should be in Arabic numerals
rather than spelled out (for example,
“120” instead of “One Hundred Twenty”).
Buildings set back in groups that
share common entrances can make
quickly locating a specific building and
the shortest route to it difficult. On such
sites, additional signs with directional
arrows and/or diagrams of the buildings
and access layout should be posted. ❑